Products

MICA GLASS TAPE, XLPE INSULATED LSFOH SHEATHED CABLES N2XH 0.6/1 KV

These cables can be used for electrcity supply and control in public network and industrial plants or public buildings, where people are potentially endangered in case of fire and where, for a defined period of time, the continuity of control and energy supply is a vital necessity.

Reference Standard

IEC 60502-1, ISIRI 3569-1

Construction

Conductor: Plain annealed copper or tinned copper stranded as per class 2 of IEC 60228
Flame barrier: Mica glass tape
Insulation: Cross-linked polyethylene -XLPE
Core identification: colour for power and black with numbers for control
Inner sheath: extruded filter of low smoke, halogen free, flame retardant -LSFOH
Outer sheath: extruded of low smoke, halogen free, flame retardant -LSFOH
standard colour is black, but any other colour can be supplied on request.

Technical Date

Temperature: -40C to +90C
Maximum short circuit temperature: 250C (5 second Max.)
Working voltage: 0.6/1.0 kv
Test Voltage: 3.5 kv rms or 8.4 kvdc for 5 minutes
Conductor resistance: As per class 2 of IEC 60228
Flame retardant test: Acc. IEC 60332-1
Flame propagation test: Acc. IEC 60332-3
Fire resistance test: Acc. IEC 60331-21
Smoke density test: Acc. IEC 61034
Halogen content test: Acc. IEC 60754-2