Products

PVC INSULATED PVC SHEATHED SINGLE AND MULTI CORE ARMOURED CABLES NYRY 0.6/1 KV

These cables can be used indoors or outdoors in cable duct, cable trays, conduit or underground location under mechanical stress in power and switching station, local distribution sytems,Industrial plants and commercial building.

Reference Standard

IEC 60502-1, VDE-0271, ISIRI 3569-1

Construction

Conductor: Plain annealed copper solid as per class 1 or 2 of IEC 60228, VDE 0295, ISIRI 3084
Insulation: Polyvinyl chloride -PVC
Core identification: colour up to 4 core and black with number printing for 5 core and above.
Inner covering: Extruded PVC compatible with operating temprature of the conductor, In sector cables the core covered with one or two layer polypropylene tape.
Screen: Concentric plain annealed copper wire applied holically over cble core, tape with open helix of copper band.
Outer sheath: Polyvinyl chloride- PVC
standard colour is black or grey, but any other colour can be supplied on request.

Technical Date

Temprature: -30C to +70C
Maximum short circuit temprature: 160C (5 second Max.)
Working voltage: 0.6/1.0 kv
Conductor resistance: As per of IEC 60228, ISIRI 3084
Test Voltage: 3.5 kv rms or 8.4 kvdc for 5 minutes
Flame retardant: Acc. IEC 60332-1