Conductor: Plain annealed copper as per class 1 or 2 of
IEC 60228, BS 6360, ISIRI 3084
Insulation: Polyethylene (PE)
Core identification: According to BS 5308 part 1
Wrapping: 1 or 2 layer of plastic tape
Collective screen: One layer aluminum/ polyester tape over copper or tinned copper drain wire, 0.5 mm2
Bedding: polyvinyl chloride – pvc
Armour: galvanized round steel wire
Outer sheath: Polyvinyl chloride (PVC), Colour can be supplied on request.
Temperature: -40C to +90C
Maximum short circuit temperature: 250C (5 second Max.)
Working voltage: 300/500 V
Test Voltage: 1.0 kv rms or 2.4 kvdc for 1 minutes
Conductor resistance: As per class 1 or 2 of IEC 60228 or BS 6360
Minimum insulation resistance: 5000 MΩ.km
Mutual capacitance at 1.0 kHz:115 nf/km for 1 or 2 pair ,75 nf/km for other cables
Flame retardant: Acc. IEC 60332-1