Products

MULTI-PAIR, PE/XLPE INSULATION COLLECTIVE SCREEN, ARMOURED PVC SHEATHED CABLES RE- 2Y(ST)YRY PIMF , RE – 2X(ST)YRY – PIMF 300/500 V

For transmission of analogue and digital signals in instrument and control system

Reference Standard

BS EN 50288- IEC 60092

Construction

Conductor: Plain annealed copper as per class 1 or 2 of

IEC 60228, BS 6360, ISIRI 3084
Insulation: Polyethylene (PE)
Core identification: According to BS 5308 part 1
Wrapping: 1 or 2 layer of plastic tape
Collective screen: One layer aluminum/ polyester tape over copper or tinned copper drain wire, 0.5 mm2
Bedding: polyvinyl chloride  – pvc
Armour: galvanized round steel wire
Outer sheath: Polyvinyl chloride (PVC), Colour can be supplied on request.

Technical Date

Temperature: -40C to +90C
Maximum short circuit temperature: 250C (5 second Max.)
Working voltage: 300/500 V
Test Voltage: 1.0 kv rms or 2.4 kvdc for 1 minutes
Conductor resistance: As per class 1 or 2 of IEC 60228 or BS 6360
Minimum insulation resistance: 5000 MΩ.km
Mutual capacitance at 1.0 kHz:115 nf/km for 1 or 2  pair ,75 nf/km for other cables

Flame retardant: Acc. IEC 60332-1