Products

MULTI – PAIR, PVC INSULATION INDIVIDUAL AND COLLECTIVE SCREEN, PVC – SHEATHED CABLES RE- Y(ST) Y – PIMF 300/500 V

For transmission of analogue and digital signals in instrument and control system

Reference Standard

BS EN 50288- IEC 60092

Construction

Conductor: Plain annealed copper as per class 1 or 2 or 5 of

IEC 60228, BS 6360, ISIRI 3084
Insulation: Polyvinyl chloride (PVC)
Core identification: According to BS 5308 part 2
Wrapping: 1 layer of plastic tape
Pair screen: One layer aluminum/polyster tape over copper or tinned copper drain wire 0.5 mm2
Collective screen: One layer aluminum/ polyester tape over copper or tinned copper drain wire, 0.5 mm2
Outer sheath: Polyvinyl chloride (PVC), Colour can be supplied on request.

Technical Date

Temperature: -30C to +70C
Maximum short circuit temperature: 150C (5 second Max.)
Working voltage: 300/500 V
Test Voltage: 1.0 kv rms or 2.4 kvdc for 1 minutes
Conductor resistance: As per class 1 or 2 or 5 of IEC 60228 or BS 6360
Minimum insulation resistance: 25 MΩ.km
Mutual capacitance at 1.0 kHz:  115 nf/km for 1 or 2  pair ,75 nf/km for other cables
Flame retardant: Acc. IEC 60332-1